The FIBERLIGN Dielectric Support (FDS) system is designed to gently, but firmly, support All-Dielectric Self-Supporting (ADSS) cable. It is intended for tangent support installations on lines that feature relatively low voltages, short spans and modest mechanical loads.

  • The approximate recommended maximum span lengths for the FDS are:
    • 600' for < 1.00" OD cable (NESC – heavy)
    • 300' for ≥ 1.00" OD cable (NESC – heavy)
  • Body and top are made from a high-strength, engineered dielectric material.  Zine plated bolts with washers secutre the top to the body.
  • Inserts are made from a soft, pliable dielectric material that gently grips the ADSS cable.
  • Threads onto standard 5/8" 11-UNC hot dipped galvanized thru-bolt
  • May be mounted horizontally or vertically
  • May be used as a stringing traveler at the structure on up to 10° line angles (20° in certain cases).
  • All components may be reused as desired if in good condition.

 

Application Procedures

SP-2742 (Fiberlign Dielectric Support ADSS)

 

Catalog Pages

Fiberlign Dielectric Support ADSS - Catalog

Ordering Instructions

For concentric ADSS cable, refer to the catalog table and select the proper FDS for the cable's outside diameter. For non-concentric profiles, such as Figure 8 or other cable sizes and profiles, consult with PLP for custom designs. To include accessories with the FIBERLIGN Dielectric Support, add code number to catalog number (example: 44002144B1)